The instructions provide information about fan replacement in

the VLT

®

 Midi Drive FC 280.

Only Danfoss authorized, qualified personnel is allowed to
repair this equipment. The personnel must be familiar with the
instructions and safety measures described in the

VLT

®

 Midi Drive FC 280 Service Guide

.

Items Supplied

Items supplied depend on ordered code number and
enclosure type of the frequency converter.

Ordering Numbers

Enclosure

Power range [kW (hp)]

Ordering number

K1

0.37–2.2 (0.5–3.0)

132B0351

K2

3.0–5.5 (4.0–7.5)

132B0352

K3

7.5 (10)

132B0353

K4

11–15 (15–20)

132B0371

K5

18.5–22 (25–30)

132B0372

Tools Required

Screwdrivers:

-

Flat-edged

-

T10

Tightening torques

0.5–0.7 Nm (4.4–6.2 in-lb)

Safety Instructions

WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. High voltage can be present even when the
warning LED indicator lights are off. Failure to wait the
specified time after power has been removed before
performing service or repair work can result in death or
serious injury.

Stop the motor.

Disconnect AC mains and remote DC-link supplies,
including battery back-ups, UPS, and DC-link
connections to other frequency converters.

Disconnect or lock PM motor.

Wait for the capacitors to discharge fully. The
minimum waiting time is specified in 

Table 1.1

.

Before performing any service or repair work, use
an appropriate voltage measuring device to make
sure that the capacitors are fully discharged.

Voltage [V]

Power range

[kW (hp)]

Minimum waiting time

(minutes)

200–240

0.37–3.7 (0.5–5)

4

380–480

0.37–7.5 (0.5–10)

4

11–22 (15–30)

15

Table 1.1 Discharge Time

Installation Instructions

Fan Replacement
VLT

®

 Midi Drive FC 280

Danfoss A/S © 11/2015 All rights reserved.

MI07D102