6-160
Object function codes
Initialize to:
E62: Terminal [C1] Extended Function
5: PID feedback value 1
E63: Terminal [V2] Extended Function
32: Auxiliary input 2 to PID process command
C64: Analog Input Adjustment for
Terminal [C1] (Display unit)
44: bar
C65: Analog Input Adjustment for
Terminal [C1] (Maximum scale)
10.00
H09: Starting Mode (Auto search)
2: Enable (At restart after momentary power
failure and at normal start)
H91: Current Input Wire Break Detection
0.5 s
J101: PID Control 1 (Mode selection)
1: Enable (Process control, normal operation)
J110: PID Control 1 P (Gain)
2.500 times
J111: PID Control 1 I (Integral time)
0.2 s
K16: Sub Monitor 1 (Display item
selection)
50: PID command (final) in physical quantity
K17: Sub Monitor 2 (Display item
selection)
51: PID feedback amount (final) in physical
quantity
When H03 = 72
(Initialize according to application (Fan))
Object function codes
Initialize to:
F02: Operation Method
1: External signals (Terminal command
FWD
or
REV
)
F07: Acceleration Time 1
3.00 s
F08: Deceleration Time 1
3.00 s
F14: Restart Mode after Momentary
Power Failure (Mode selection)
3: Continue to run, for heavy inertia or general
loads
F15: Frequency Limiter (High)
50.0 Hz
F16: Frequency Limiter (Low)
20.0 Hz
F26: Motor Sound (Carrier frequency)
3 kHz
F35: Pulse Output [FM2] (Function)
2: Output current
F37: Load Selection
3: Auto energy saving (Variable torque load
during ACC/DEC)
F42: Drive Control Selection 1
1: Dynamic torque vector control
H09: Starting Mode (Auto search)
2: Enable (At restart after momentary power
failure and at normal start)
H69: Automatic Deceleration (Mode
selection)
5: DC link bus voltage control with
Force-to-stop disabled
H71: Deceleration Characteristics
1: Enable
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...