6.3 Details of Function Codes
6-263
Chap. 6
FUNCTION C
ODES
[ 2 ] PID control action
In the inverter-driven motor floating system (J401 = 2), the following state (1) or (2) is
developed depending on the setting of motor mode selection (J411 to J418).
(1) Driving of all motors are not permitted
When driving of all motors is not permitted (pump control drive motor permission
commands 1 to 8 = OFF ("MEN1" to "MEN8") or the motors are set to disable with
motor mode selection (J411 to J418), PID control will not start because no motors can
control the pump.
(2) All motors are driven by commercial power forcibly
On changing all motors from forced commercial power drive state to enable state ("2
⇒
1" for J411 to J418) with the run command turned ON, motor increase/decrease
judgment will be performed immediately based on the PID control.
J425
Motor Switching Procedure
In pump control, two or more motors are operated while switching them. When increasing or
decreasing the number of operating motors, specify the motors to be driven and the motors to
be stopped in the motor switching procedure (J425). This allows cumulative run time for each
motor to be equalized.
- Data setting range: 0 to 3
Data for J425
Function
0
Fixing procedure
<When the number of motors increases>
The number increases successively in order of increasing the motor number.
(motor 1
⇒
motor 2, motor 3...)
<When the number of motors decreases>
The number decreases successively in order of decreasing the motor number.
(motor 3
⇒
motor 2, motor 1...)
1
Equal operating time (Cumulative run time of each motor is equalized.)
<When the number of motors increases>
Of the motors that are not running, turn on the motor having the shortest
operating time.
<When the number of motors decreases>
Of the motors that are running, turn off the motor having the longest operating
time.
2
Fixing procedure (Switching the motor at slow flowrate stop)
Mode selection is the same when J425 is configured to 0. However, the drive
motor switches to the subsequent motor not only when motors are increased,
but also during slow flowrate stop.
3
Equal operating time (Switching the motor at slow flowrate stop)
The operation is the same as when J425 =1 is selected. However, the drive
motor switches to the motor with least operating time not only when motors
are increased, but also during slow flowrate stop.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...