6.3 Details of Function Codes
6-299
Chap. 6
FUNCTION C
ODES
J527
J529
J530
J531
External PID Control 1 (Feedback error detection mode)
(Feedback error upper-limit)
(Feedback error lower-limit)
(Feedback error detection time)
J627 (External PID Control 2 (Feedback error detection mode)
J629 (External PID Control 2 (Feedback error upper-limit)
J630 (External PID Control 2 (Feedback error lower-limit)
J631 (External PID Control 2 (Feedback error detection time)
J677 (External PID Control 3 (Feedback error detection mode)
J679 (External PID Control 3 (Feedback error upper-limit)
J680 (External PID Control 3 (Feedback error lower-limit)
J681 (External PID Control 3 (Feedback error detection time)
Under external PID control, the inverter can detect abnormal feedback values (PV).
In the case of external PID control 1, if the error level of a PV signal (Upper limit: J529,
Lower limit: J53) is kept for the feedback error detection time (J531), the inverter regards it as
an error, then stops or continues running according to the mode specified by J527.
The table below lists the function codes available for external PID control 1, 2 and 3.
Feedback error
detection mode
Feedback error
upper limit
Feedback error
lower limit
Error detection
time
External PID
control 1
J527 J529 J530 J531
External PID
control 2
J627 J629 J630 J631
External PID
control 3
J677 J679 J680 J681
External PID control 1 to 3 (Feedback error detection mode) (J527, J627, J677)
J527/J627/J677 specifies the error processing to be performed if a feedback error occurs.
- Data setting range: 0 to 2
Data for
J527/J627/J677
Error processing
0
Disable: Turn ON the following output signal and continue to run.
EPV1-OFF
for external PID control 1
EPV2-OFF
for external PID control 2
EPV3-OFF
for external PID control 3
1
Enable: Coast to a stop (PVA trip)
2
Enable: Decelerate to a stop and cause a PVA trip.
Feedback errors can be monitored from the external equipment by assigning the digital output
signal
EPV1-OFF
,
EPV2-OFF
or
EPV3-OFF
to any of the output terminals [Y1] to [Y4],
[Y5A/C], and [30A/B/C] with any of E20 through E24 and E27.
- External PID control 1:
EPV1-OFF
(E20 to E24 and E27, data = 215)
- External PID control 2:
EPV2-OFF
(E20 to E24 and E27, data = 225)
- External PID control 3:
EPV3-OFF
(E20 to E24 and E27, data = 235)
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...