4.4 Options
4-35
Chap. 4
SEL
ECT
ING PE
RIPH
ER
AL
EQUI
PME
N
T
4.4.1.3 DC reactors (DCRs) (Built-in or bundled as standard)
Inverters of 90 kW or below have a DCR built-in as standard. Those of 110 kW or above have a DCR
bundled as standard, so be sure to connect it to the inverter in accordance with the reference wiring
diagram.
A DCR has the following effects.
For power supply matching
- Use a DCR when the capacity of a power supply transformer exceeds 500 kVA and is 10 times or
more the rated inverter capacity. In this case, the percent reactance of the power supply decreases,
and harmonic components and their peak value increase. These factors may break rectifiers or
capacitors in the converter section of inverter, or decrease the capacitance of the capacitor (which
can shorten the inverter's service life).
- Also use a DCR when there are thyristor-driven loads or when phase-advancing capacitors are
being turned ON/OFF.
- Use a DCR when the interphase voltage unbalance ratio of the inverter power supply exceeds 2%.
67
×
V)
(
voltage
average
phase
-
Three
V)
(
voltage
Min.
V)
(
voltage
Max.
=
%)
(
unbalance
voltage
Interphase
For input power factor correction (for suppressing harmonics)
Generally a capacitor is used to improve the power factor of the load, however, it cannot be used in a
system that includes an inverter. Using a DCR increases the reactance of inverter's power supply so as
to decrease harmonic components on the power supply lines and improve the power factor of inverter.
Using a DCR improves the input power factor to approximately 86% to 95%.
Table 4.7 DC Reactors (DCRs)
Power
supply
voltage
Nominal
applied
motor
(kW)
Inverter type
DC reactor type
Rated current
(A)
Inductance
(mH)
Generated loss
(W)
110 FRN110AQ1S-4
DCR4-110C
261
0.166
122
132 FRN132AQ1S-4
DCR4-132C
313
0.148
159
160 FRN160AQ1S-4
DCR4-160C
380
0.122
185
200 FRN200AQ1S-4
DCR4-200C
475
0.098
218
220 FRN220AQ1S-4
DCR4-220C
524
0.087
231
280 FRN280AQ1S-4
DCR4-280C
649
0.069
270
315 FRN315AQ1S-4
DCR4-315C
739
0.061
285
355 FRN355AQ1S-4
DCR4-355C
833
0.054
308
400 FRN400AQ1S-4
DCR4-400C
938
0.048
323
500 FRN500AQ1S-4
DCR4-500C
1173
0.039
384
630 FRN630AQ1S-4
DCR-630C
1477
0.031
620
Three-
phase
400 V
710 FRN710AQ1S-4
DCR-710C
1666
0.028
600
Note 1:
A box (
) replaces an alphabetic letter depending on the shipping destination.
E (EU), A (Asia), or C (China)
Note 2:
Generated losses listed in the above table are approximate values that are calculated according to the
following conditions:
- The power supply is three-phase 400 V 50 Hz with 0% interphase voltage unbalance ratio.
- The power supply capacity uses the larger of either 500 kVA or 10 times the rated capacity of the inverter.
- The motor is a 4-pole standard model at full load (100%).
- An AC reactor (ACR) is not connected.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...