6.3 Details of Function Codes
6-335
Chap. 6
FUNCTION C
ODES
Communications error processing (y02 for port 1 and y12 for port 2)
y02 or y12 specifies the error processing to be performed if an RS-485 communications error
occurs.
RS-485 communications errors include logical errors (e.g., address error, parity error,
framing error), transmission protocol error, and physical errors (e.g., no-response error
specified by y08 and y18). The inverter can recognize such an error only when it is
configured with a run or frequency command sourced through the RS-485 communications
link and it is running.
Data
for y02, y12
Function
0
Immediately trip, displaying an RS-485 communications error (Er8 for y02
and ErP for y12). (The inverter stops with alarm issue.)
1
Run during the period specified by the error processing timer (y03, y13),
display an RS-485 communications error (Er8 for y02 and ErP for y12), and
then stop operation. (The inverter stops with alarm issue.)
2
Retry communication during the period specified by the error processing timer
(y03, y13). If a communications link is recovered, continue operation.
Otherwise, display an RS-485 communications error (Er8 for y02 and ErP for
y12) and stop operation. (The inverter stops with alarm issue.)
3
Continue to run even when a communications error occurs.
For details, refer to the RS-485 Communication User's Manual.
Timer (y03 for port 1 and y13 for port 2)
y03 or y13 specifies an error processing timer.
If the specified timer count has elapsed due to no response from the other end when a query
has been issued, the inverter interprets it as an error occurrence. See the "No-response error
detection time (y08, y18)" given on the next page.
- Data setting range: 0.0 to 60.0 (s)
Baud rate (y04 for port 1 and y14 for port 2)
Data for
y04 and y14
Transmission speed (bps)
0 2400
1 4800
2 9600
3 19200
y04 or y14 specifies the transmission speed
for RS-485 communication.
For FRENIC Loader (via the RS-485
communications link), specify the
transmission speed that matches the
connected computer.
4 38400
Data length (y05 for port 1 and y15 for port 2)
Data for
y05 and y15
Data length
0 8
bits
1 7
bits
y05 or y15 specifies the character length for
RS-485 communication.
For FRENIC Loader (via the RS-485
communications link), no setting is required
since Loader automatically sets 8 bits. (The
same applies to the Modbus RTU protocol.)
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...