6-186
H96
STOP Key Priority/Start Check Function
H96 specifies a functional combination of "STOP key priority" and "Start check function" as
listed below.
Data for H96
STOP key priority
Start check function
0 Disable
Disable
1
Enable
Disable
2
Disable
Enable
3
Enable
Enable
STOP key priority
Even when a run command is entered from a digital input terminal or via the RS-485
communications link (link operation), pressing the
key forces the inverter to decelerate to
stop the motor. After that, an Er6 alarm occurs.
Start check function
For safety, this function checks whether any run command has been turned ON or not in each
of the following situations. If any has been turned ON, the inverter does not start up with
alarm code Er6 displayed.
• When the power to the inverter is turned ON.
• When the
key is pressed to release an alarm status or when the digital input terminal
command
RST
("Reset alarm") is turned ON.
• When the run command source is switched by a digital input terminal command such as
LE
("Enable communications link via RS-485 or fieldbus") or
LOC
("Select local (keypad)
operation").
H97
Clear Alarm Data
H45 (Mock Alarm)
H97 clears alarm data (alarm history and relevant information) stored in the inverter. To clear
alarm data, simultaneous keying of "
key +
key" is required.
Data for H97
Function
0 Disable
1
Enable
(Setting "1" clears alarm data and then returns to "0.")
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...