6.2 Function Code Tables
6-3
Chap. 6
FUNCTION C
ODES
The following tables list the function codes available for the FRENIC-AQUA series of inverters.
F codes: Fundamental Functions
Code Name
Data
setting
range
Change
when
running
Data
copying
Default
setting
F00 Data Protection
0: Disable both data protection and digital reference protection
1: Enable data protection and disable digital reference protection
2: Disable data protection and enable digital reference protection
3: Enable both data protection and digital reference protection
Y Y 0
F01 Frequency Command 1
0:
/ / / keys on keypad
1: Voltage input to terminal [12] (-10 to +10 VDC)
2: Current input to terminal [C1] (4 to 20 mA DC)
3: Sum of voltage and current inputs to terminals [12] and [C1]
5: Voltage input to terminal [V2] (0 to 10 VDC)
7: Terminal command
UP/DOWN
control
8:
/ / / keys on keypad
(balanceless-bumpless switching available)
10: Pattern operation
N Y 0
F02 Operation Method
0: FWD/REV/STOP keys on keypad (Motor rotational direction
specified by terminal command
FWD
/
REV
)
1: External signals (Terminal command
FWD
or
REV
)
2: FWD/STOP keys on keypad (forward)
3: REV/STOP keys on keypad (reverse)
N Y 0
F03 Maximum Frequency 1
25.0 to 120.0 Hz
N Y
50.0
F04 Base Frequency 1
25.0 to 120.0 Hz
N Y
50.0
F05 Rated Voltage at Base Frequency 1
0: Output a voltage in proportion to input voltage
160 to 500 V: Output an AVR-controlled voltage
N Y
F06 Maximum Output Voltage 1
160 to 500 V: Output an AVR-controlled voltage
N Y
E: 400
A: 415
C: 380
F07 Acceleration
Time
1
Y Y
20.00
F08 Deceleration
Time
1
0.00 to 3600.00 s
Note: Entering 0.00 cancels the acceleration time, requiring
external soft-start.
Y Y
20.00
F09 Torque Boost 1
0.0% to 20.0% (percentage with respect to "F05: Rated Voltage at
Base Frequency 1")
Y Y *1
F10 Electronic Thermal Overload Protection for
Motor 1
(Select motor characteristics)
1: For a general-purpose motor with shaft-driven cooling fan
2: For an inverter-driven motor, non-ventilated motor, or motor
with separately powered cooling fan
Y Y 1
F11
(Overload detection level) OFF: Disable
1% to 135% of the inverter rated current
Y Y1 *3
F12
(Thermal time constant) 0.5 to 75.0 min
Y Y *2
F14 Restart Mode after Momentary Power
Failure (Mode
selection)
0: Trip immediately
1: Trip after a recovery from power failure
3: Continue to run, for heavy inertia or general loads
4: Restart at the frequency at which the power failure occurred,
for general loads
5: Restart at the starting frequency
Y Y
E:
0
A/C: 1
F15 Frequency Limiter
(High) 0.0 to 120.0 Hz
Y Y
70.0
F16
(Low) 0.0 to 120.0 Hz
Y Y 0.0
F18 Bias
(Frequency command 1) -100.00% to 100.00%
Y* Y 0.00
F20 DC Braking 1
(Braking
starting
frequency)
0.0 to 60.0 Hz
Y Y 0.0
F21
(Braking level) 0% to 60%
on the basis of inverter rated current
Y Y 0
F22
(Braking time) OFF (Disable); 0.01 to 30.00 s
Y Y
OFF
F23 Starting Frequency 1
0.1 to 60.0 Hz
Y Y 0.5
F24
(Holding time) 0.00 to 10.00 s
Y Y
0.00
F25 Stop Frequency
0.1 to 60.0 Hz
Y Y 0.2
F26 Motor Sound
(Carrier frequency) 0.75 to 16 kHz (0.75 to 37 kW)
0.75 to 10 kHz (45 to 90 kW)
0.75 to 6 kHz (110 to 630 kW)
0.75 to 4 kHz (710 kW)
Y Y 2
F27
(Tone) 0: Level 0 (Inactive)
1: Level 1
2: Level 2
3: Level 3
Y Y 0
F29 Analog Output [FM1]
(Mode selection) 0: Output in voltage (0 to 10 VDC)
1: Output in current (4 to 20 mA DC)
2: Output in current (0 to 20 mA DC)
Y Y 0
F30
(Voltage adjustment) 0% to 300%
Y* Y 100
The shaded function codes (
) are applicable to the quick setup.
Note: Alphabets in the Default setting field denote shipping destination: E (EU), A (Asia), C (China).
*1 The factory default differs depending upon the inverter's capacity. See Table A.
*2 5.0 min for inverters with a capacity of 22 kW or below; 10.0 min for those with 30 kW or above
*3 The motor rated current is automatically set. See Table B (function code P03).
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...