6-140
Example: To detect 0 to 30 kPa with 4 to 20 mA output of the pressure sensor
1) Input monitor
Set E62 (Terminal [C1] extended function) to "20."
2) Scale
- Maximum scale (C65): Set 30.0 to be displayed when the analog input value on
terminal [C1] is 100%.
- Minimum scale (C66): Set 0 to be displayed when the analog input value on terminal
[C1] is 0%.
*The display unit should be selected with C64.
C67
Analog Input Adjustment for Terminal [V2] (Bias value)
(Refer to F01.)
C67 specifies a bias value to Reference frequency 2 and analog input monitor terminal [V2].
For details, refer to the description of F01.
C68
Analog Input Adjustment for Terminal [V2] (Bias base point)
(Refer to F01.)
C68 specifies a bias base point for Reference frequency 2 and analog input monitor terminal
[V2]. For details, refer to the description of F01.
C70
Analog Input Adjustment for Terminal [V2] (Display unit)
C70 specifies the display unit for analog input monitor, PID control commands and feedback
amounts on terminal [V2].
The specified display unit appears when analog input monitor, SV and PV are displayed on
the main or sub monitor.
Data for
C70
Display unit
Data for
C70
Display unit
Data for
C70
Display unit
1
No display unit
24
L/min (Flowrate)
46
Psi (Pressure)
2 %
25 L/h
(Flowrate)
47 mWG
(Pressure)
4 r/min
40 Pa
(Pressure)
48 inWG
(Pressure)
7 kW
41 kPa
(Pressure)
60 K
(Temperature)
20 m
3
/s (Flowrate)
42
MPa (Pressure)
61
°
C (Temperature)
21 m
3
/min (Flowrate)
43
mbar (Pressure)
62
°
F (Temperature)
22 m
3
/h (Flowrate)
44
bar (Pressure)
80
ppm (Density)
23 L/s
(Flowrate)
45 mmHg
(Pressure)
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...