9-6
Possible Causes
What to Check and Suggested Measures
(3) The power supply voltage did
not reach the inverter's
specification range.
Measure the input voltage.
Î
Increase the voltage to within the specified range.
(4) Peripheral equipment for the
power circuit malfunctioned, or
the connection was incorrect.
Measure the input voltage to find which peripheral equipment
malfunctioned or which connection is incorrect.
Î
Replace any faulty peripheral equipment, or correct any incorrect
connections.
(5) Any other loads connected to
the same power supply have
required a large starting
current, causing a temporary
voltage drop.
Measure the input voltage and check the voltage fluctuation.
Î
Reconsider the power supply system configuration.
(6) Inverter's inrush current caused
the power voltage drop because
the power supply transformer
capacity was insufficient.
Check if the alarm occurs when a molded case circuit breaker (MCCB),
residual-current-operated protective device (RCD)/earth leakage circuit
breaker (ELCB) (with overcurrent protection) or magnetic contactor
(MC) is turned ON.
Î
Reconsider the capacity of the power supply transformer.
[ 5 ] Lin Input phase loss
Problem Input phase loss occurred, or interphase voltage unbalance rate was large.
Possible Causes
What to Check and Suggested Measures
(1) Breaks in wiring to the main
power input terminals.
Measure the input voltage.
Î
Repair or replace the main circuit power input wires or input
devices (MCCB, MC, etc.).
(2) The screws on the main power
input terminals are loosely
tightened.
Check if the screws on the main power input terminals have become
loose.
Î
Tighten the terminal screws to the recommended torque.
(3) Interphase voltage unbalance
between three phases was too
large.
Measure the input voltage.
Î
Connect an AC reactor (ACR) to lower the voltage unbalance
between input phases.
Î
Increase the inverter capacity.
(4) Overload cyclically occurred.
Measure the ripple wave of the DC link bus voltage.
Î
If the ripple is large, increase the inverter capacity.
(5) Single-phase voltage was input
to the three-phase input
inverter.
Check the inverter type.
Î
Apply three-phase power. The FRENIC-AQUA of three-phase
input cannot be driven by single-phase power.
The input phase loss protection can be disabled with the function code H98
(Protection/Maintenance Function).
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...