6-246
Function code
Name
Data
Description
E01 to E07
[X1] to [X7]
151 to 158:
MEM1
to
MEM8
Pump control motor 1
to 8
These function codes individually separate
pumps from the inverter drive motor fixed
system with external signals.
Only pumps whose
MEM
signals are ON are
subject to this system.
J465 Auxiliary
motor
(Frequency
operation level)
OFF, 0.1 to 120 Hz
J466 Auxiliary
motor
(Hysteresis
width)
0.0 to 120 Hz
When all pumps subject to this system are
operating and the inverter output exceeds the
setting of J465, the auxiliary pump start signal
comes ON.
If the inverter decelerates from the setting of
J465 by the setting of J466, the auxiliary pump
start signal goes OFF.
Each function code is detailed separately.
Cascade control (Inverter drive motor floating system)
To switch a maximum of four pumps between inverter drive and commercial power drive by a single
FRENIC-AQUA, configure two magnetic contactors per pump.
The FRENIC-AQUA drives the first pump at variable speed under PID control. If the frequency rises
due to a PV signal level drop to satisfy the pump adding conditions, the FRENIC-AQUA switches the
inverter-driven pump to commercial power drive and drives the newly added pump. After starting all
pumps, the inverter can further drive a single auxiliary pump (MA). If the PV signal level rises and the
frequency of the inverter-driven pump drops to satisfy the pump subtracting conditions, the
FRENIC-AQUA cancels start signals of the pumps being driven by commercial power, thereby
stopping them successively. At the time of decreasing pumps, the FRENIC-AQUA continues to drive
the last added pump.
In this system, each of pumps to be controlled requires two signal lines for inverter drive and
commercial power drive. To operate the pump drive system in a maximum configuration, an auxiliary
pump start signal line is further required.
The number of start signal lines available on the FRENIC-AQUA is a total of six--four transistor
output lines and two relay output lines in a standard configuration, so the FRENIC-AQUA can control
a total of three pumps in a standard configuration.
To operate the pump drive system using four or more pumps, it is necessary to add the optional relay
output card (OPC-RY2) to the FRENIC-AQUA. It can add seven relay output lines.
The advantage of this system is that the operating times of pumps can be averaged since the
FRENIC-AQUA cycles through pump motors.
Cascade control (Inverter drive motor fixed + commercial power-driven motor system)
This system is the same as the inverter drive motor floating system in the basic configuration, except
that it fixes the inverter drive pump according to the slow flowrate unit and switches the inverter drive
pump when the system is started at the next time.
The advantage of this system is that the ON/OFF times of the magnetic contactors can be reduced.
Therefore, this system is suitable for clean water supply systems repeating slow flowrate stops
frequently.
Summary of Contents for FRENIC-AQUA series
Page 1: ...MEHT538b...
Page 2: ...User s Manual...
Page 13: ......
Page 15: ......
Page 33: ......
Page 35: ......
Page 61: ...2 26 Figure D Figure E NC No connection Do not make wiring NC NC...
Page 63: ...2 28 Figure J Figure K Charging lamp Charging lamp Viewed from A...
Page 83: ...2 48 Unit mm FRN45 to 55AQ1 4...
Page 84: ...2 9 External Dimensions 2 49 Chap 2 SPECIFICATIONS Unit mm FRN75 to 90AQ1 4...
Page 85: ...2 50 Unit mm FRN110AQ1S 4 FRN132AQ1S 4 FRN160AQ1S 4 FRN200AQ1S 4...
Page 87: ...2 52 Unit mm FRN500AQ1S 4 FRN630AQ1S 4 FRN710AQ1S 4...
Page 88: ...2 9 External Dimensions 2 53 Chap 2 SPECIFICATIONS 2 9 2 Keypad Unit mm Panel cutout...
Page 95: ......
Page 140: ...4 4 Options 4 33 Chap 4 SELECTING PERIPHERAL EQUIPMENT...
Page 279: ......
Page 281: ......
Page 341: ...6 60 Example of Thermal Overload Detection Characteristics...
Page 637: ......
Page 639: ......
Page 651: ...7 12 Figure 7 7 Terminal FM2 Output Selector...
Page 653: ......
Page 663: ......
Page 665: ......
Page 699: ......
Page 717: ......
Page 719: ......
Page 733: ......
Page 749: ......
Page 751: ...MEHT537 Phone 81 3 5435 7058 Fax 81 3 5435 7420 Printed in Japan 2012 08 H12b b12 CM00FOLS...