8-30
Parameters
CLM01.4-LAP-01VRS
DOK-CONTRL-CLM01.4LAP1-FK01-EN-P
B006 Fieldbus Time Monitoring
F i e l d b u s
T i m e M o n
B 0 0 6
1 2 3 4 5
Maximum cycle time in ms
Cyclic transmission of the process data via the fieldbus is monitored. If no
new message is received within the maximum cycle time, the control unit
generates the following error message:
37 Fieldbus Timeout
If the cycle time is preset by the fieldbus master, the actually used value is
written to this parameter and can be read out for diagnostic purposes.
Note:
A value of 0 means that monitoring is turned off!
For further information, see the Fieldbus chapter.
B007 Fieldbus Baudrate
F i e l d b u s B a u d r a t e
B 0 0 7
1 2 3 4 5 6 . 7
Fieldbus Baudrate in kBaud
Here, the desired baud rate in increments of 1 kBaud can be set, if the
fieldbus does not automatically detect the baud rate. If the set baud rate is
not allowed, a default baud rate for the particular fieldbus is used. The
actually used value is written to this parameter and can be read out for
diagnostic purposes.
For further information, see the Fieldbus chapter.