9-16
Interfaces
CLM01.4-LAP-01VRS
DOK-CONTRL-CLM01.4LAP1-FK01-EN-P
Interface Parameters
B002 Interface Format X6
R S - F o r m a t
X 6
B 0 0 2
0 0 9 6 0 0
0
1
8
1
Number of stop bits (1 or 2)
Word length in bits (7 or 8)
Parity check
1 = no parity
2 = even
3 = odd
Interface operation
0 = standard RS232C/RS422 full duplex
1 = decade switch IDS01 (2400 baud, 8 data bits, 1 stop bit, no parity)
2 = like 0
3 = RS485, half-duplex, station number 01
4 = RS485, half-duplex, station number 1 - 32
Baud rate (300 to 115200 baud)
000000 = interface is disabled
The CLM’s serial interface can exchange data with the system in different
ways. The selected transmission format is defined in Parameter B002: If
the decade switch input is preselected via an IDS01 unit, the other values
need not be input.
The desired baud rate can be selected from the following list of values:
Baud
Rate
300
600
1200
2400
4800
9600
19200
38400
57600
115200
An input of ’000000’ means that the interface is off.
Baud Rate: