CLM01.4-LAP-01VRS
Terminal Connection Diagrams
12-5
DOK-CONTRL-CLM01.4LAP1-FK01-EN-P
12.7 RS232C/RS485 Data Interface – Serial Channel A
Connector X6
7
3
2
1
0V
RxD
TxD
Communication Port RS 232
Cable: IKS 741
Decade switch option IDS
pink 0,5 mm2
gray 0,5 mm2
yellow
brown
white
yellow/green
24
8
7
3
2
1
RxD
TxD
Communication Port RS 232
Cable: IKS 742
Connector X6
External Interface
21
20
17
18
12
11
7
22
23
(Rx-Tx)
(Rx-Tx)+
GND
+24V
0V
brown 0,22 mm2
white 0,22 mm2
green 0,22 mm2
Shield
(Rx-Tx)
(Rx-Tx)+
SGND
+5V
GND
Communication Port RS 485
CABLE: IKS 754
5
4
3
2
1
Connector X2
5V
0V
0V
TxD
RxD
gray 0,5 mm2
brown
white
yellow/green
Cable length up to 600 m
The shield must be contacted with the
connector housing using the metallic
sleeve into the connector!
Connector X6
150R
390R
390R
499R
499R
+5V
GND
C14X06aP1_AE.WMF
Fig. 12-6: Connector X6 – RS232C/RS485 Data Interface – Serial Channel A