3-6
Safety Instructions for Electric Drives and Controls
CLM01.4-LAP-01VRS
DOK-CONTRL-CLM01.4LAP1-FK01-EN-P
To be observed with electrical drive and filter components:
DANGER
High electrical voltage on the housing!
High leakage current! Danger to life, danger of
injury by electric shock!
⇒
Connect the electrical equipment, the housings of all
electrical units and motors permanently with the safety
conductor at the ground points before power is
switched on. Look at the connection diagram. This is
even necessary for brief tests.
⇒
Connect the safety conductor of the electrical
equipment always permanently and firmly to the
supply mains. Leakage current exceeds 3.5 mA in
normal operation.
⇒
Use a copper conductor with at least 10 mm² cross
section over its entire course for this safety conductor
connection!
⇒
Prior to startups, even for brief tests, always connect
the protective conductor or connect with ground wire.
Otherwise, high voltages can occur on the housing
that lead to electric shock.
3.6
Protection Against Electric Shock by Protective Low
Voltage (PELV)
All connections and terminals with voltages between 0 and 50 Volts on
Rexroth Indramat products are protective low voltages designed in
accordance with international standards on electrical safety.
WARNING
High electrical voltage due to wrong
connections! Danger to life, bodily harm by
electric shock!
⇒
Only connect equipment, electrical components and
cables of the protective low voltage type (PELV =
Protective Extra Low Voltage) to all terminals and
clamps with voltages of 0 to 50 Volts.
⇒
Only electrical circuits may be connected which are
safely isolated against high voltage circuits. Safe
isolation is achieved, for example, with an isolating
transformer, an opto-electronic coupler or when
battery-operated.
Summary of Contents for CLM1.4
Page 117: ...7 20 Functions CLM01 4 LAP 01VRS DOK CONTRL CLM01 4LAP1 FK01 EN P Notes...
Page 205: ...9 42 Interfaces CLM01 4 LAP 01VRS DOK CONTRL CLM01 4LAP1 FK01 EN P Notes...
Page 213: ...10 8 Command Communications CLM01 4 LAP 01VRS DOK CONTRL CLM01 4LAP1 FK01 EN P Notes...
Page 233: ...11 20 Diagnostic Messages CLM01 4 LAP 01VRS DOK CONTRL CLM01 4LAP1 FK01 EN P Notes...
Page 272: ......
Page 273: ...Printed in the U S A Barcode...