5 - 84
MELSEC-Q
5 DATA USED FOR POSITIONING CONTROL
Storage item
Storage details
Reading the monitor value
Md.7
Error
judgment
[Storage details]
This area stores the following results of the error judgment performed
upon starting:
•
BUSY start warning flag
•
Error flag
•
Error No.
[Reading the monitor value]
Monitoring is carried out with a hexadecimal display.
b15
b12
b8
b4
b0
A
B
C
D
B
a
C
D
Monitor value
D
C
B
A
Stored contents
Storage value
0
1
Stored contents
Storage value
0
1
Buffer
memory
Error flag OFF
Error flag ON
BUSY start
warning OFF
BUSY start
warning ON
Convert the hexadecimal value "a, B, C, D" into a decimal value and
match it with "15.3 List of errors".
Error flag
BUSY start warning flag
Error No.
Starting history (U
p to 16 records can be stored)
Md.8
Start history
pointer
Indicates a pointer No. that
is next to the Pointer No.
assigned to the latest of the
existing starting history
records.
Monitoring is carried out with a decimal display.
Monitor value
Storage value (Pointer number)
0 to 15
Summary of Contents for Melsec-Q QD75D1
Page 1: ......
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Page 292: ...MEMO ...
Page 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Page 857: ......
Page 858: ......