12 - 100
MELSEC-Q
12 CONTROL SUB FUNCTIONS
[2] Control precautions
(1) The time required to analyze the positioning data is up to 7ms.
(2) After positioning data analysis, the system is put in an execution prohibition
flag OFF waiting status. Any change made to the positioning data in the
execution prohibition flag OFF waiting status is not reflected on the
positioning data. Change the positioning data before turning ON the
positioning start signal.
(3) The pre-reading start function is invalid if the execution prohibition flag is
turned OFF between when the positioning start signal has turned ON and
when positioning data analysis is completed (Ta<start time, Ta: Refer to Fig.
12.49).
(4) The data No. which can be executed positioning start using "
Cd.3
Positioning
start No." with the pre-reading start function are No. 1 to 600 only. Performing
the pre-reading start function at the setting of No. 7000 to 7004 or 9001 to
9004 will result in an error "Outside start No. range" (error code: 543).
(5) Always turn ON the execution prohibition flag at the same time or before
turning ON the positioning start signal. Pre-reading may not be started if the
execution prohibition flag is turned ON during Ta after the positioning start
signal is turned ON. The pre-reading start function is invalid if the execution
prohibition flag is turned ON after positioning start (pulse output) with the
execution prohibition flag OFF. (It is made valid at the next positioning start.)
[3] Program examples
Pre-reading start function (when positioning start signal Y10 is used)
<Pre-reading start command pulse>
<Sets 1 to positioning start No.>
<Turns ON execution prohibition flag>
<Turns ON positioning start signal>
<Turns OFF execution prohibition flag>
<Turns OFF positioning start signal>
Summary of Contents for Melsec-Q QD75D1
Page 1: ......
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Page 292: ...MEMO ...
Page 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Page 857: ......
Page 858: ......