15 - 38
MELSEC-Q
15 TROUBLESHOOTING
Classification
of errors
Error
code
Error name
Error
Operation status at error occurrence
981 OPR direction error
The set value of the OPR basic
parameter "OPR direction" is outside
the setting range.
982
OP address setting
error
The set value of the OPR basic
parameter "OP address" is outside
the setting range.
983 OPR speed error
• The set value of the OPR basic
parameter "OPR speed" is outside
the setting range.
• The set value of the OPR basic
parameter "OPR speed" is smaller
than the bias speed at start.
984 Creep speed error
• The set value of the OPR basic
parameter "Creep speed" is outside
the setting range.
• The set value of the OPR basic
parameter "Creep speed" is larger
than the OPR speed.
• The set value of the OPR basic
parameter "Creep speed" is
smaller than the bias speed at
start.
985 OPR retry error
The set value of the OPR basic
parameter "OPR retry" is outside the
setting range.
991
Setting for the
movement amount
after near-point dog
ON error
The set value of the OPR detailed
parameter "Setting for the movement
amount after near-point dog ON" is
outside the setting range.
992
OPR acceleration
time selection error
The set value of the OPR detailed
parameter "OPR acceleration time
selection" is outside the setting
range.
993
OPR deceleration
time selection error
The set value of the OPR detailed
parameter "OPR deceleration time
selection" is outside the setting
range.
995
OPR torque limit
value error
• The set value of the OPR detailed
parameter "OPR torque limit value"
is outside the setting range.
• The OPR detailed parameter "OPR
torque limit value" has exceeded
the detailed parameter 1 "Torque
limit setting value".
996
Deviation counter
clear signal output
time setting error
The set value of the OPR detailed
parameter "Deviation counter clear
signal output time" is outside the
setting range.
Parameter
997
Speed designation
during OP shift error
The set value of the OPR detailed
parameter "Speed designation
during OP shift" is outside the setting
range.
The QD75 READY signal (X0) is not
turned ON.
Summary of Contents for Melsec-Q QD75D1
Page 1: ......
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Page 292: ...MEMO ...
Page 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Page 857: ......
Page 858: ......