14 - 6
MELSEC-Q
14 DEDICATED INSTRUCTIONS
(4) Using the Z.ABRST instruction, the absolute position restoration is carried out in
the following procedure.
End
Output the ((S)+3) data.
Is ((S)+4) "0"?
Other than "0"
0
Set the ABS data bit 0/bit 1 and transmission data READY flag
using the sequence program.
Output the servo ON, ABS transfer mode, and ABS request flag
to the output module using the sequence program.
Start
. . . . . . . . .
. . . . . . . . .
Execute the Z.ABRST instruction.
Set the data in ((S)+2).
[Errors]
(1) When a dedicated instruction is completed abnormally, the error complete signal
((D)+1) is turned ON, and the error code is stored in the complete status ((S)+1).
Check and take a measure against the error referring to Section 15.3 "List of error
codes".
[Precautions]
(1) After the absolute position detection system is configured, the absolute position
restoration must be carried out at least once after the power is turned ON or reset.
Unless the absolute position restoration of the QD75 is completed, the servo
amplifier will not be turned ON.
(2) Execute absolute position restoration when the PLC READY signal [Y0] is OFF.
(3) The restoration of the absolute position (Z.ABRST instruction execution) can
also be carried out when the servo amplifier is turned ON. If this is carried out,
however, the servo ON signal is turned OFF for approx. 60ms + scan time (servo
OFF) and the motor may move.
When carrying out the absolute position restoration during servo OFF, install an
electromagnetic brake and output the Z.ABRST instruction to that brake during
the Z.ABRST instruction execution.
(4) The following dedicated instructions cannot be executed simultaneously for the
same axis.
(Can be executed simultaneously for different axes.)
• Positioning start instructions (ZP.PSTRT1 to ZP.PSTRT4)
• Absolute position restoration instructions (Z.ABRST1 to Z.ABRST4)
• Teaching instructions (ZP.TEACH1 to ZP.TEACH4)
(5) When the remote I/O station (Q Corresponding MELSECNET/H network remote
I/O module) is used, the dedicated instruction (Z.ABRST ) is unusable.
(For the sequence program example for use when the dedicated instruction is not
used, refer to the Mitsubishi General-Purpose AC Servo "Absolute Position
Detection System" Installation Guide.)
: For details of the remote I/O station, refer to Q Corresponding MELSECNET/H
Network System Reference Manual (Remote I/O Network).
Summary of Contents for Melsec-Q QD75D1
Page 1: ......
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Page 292: ...MEMO ...
Page 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Page 857: ......
Page 858: ......