12 CONTROL SUB FUNCTIONS
12.7.2 Skip function
The "skip function" is used to stop (deceleration stop) the control of the positioning
data being executed at the time of the skip signal input, and execute the next
positioning data.
A skip is executed by a skip command (
Cd.37
Skip command) or external command
signal.
The "skip function" can be used during control in which positioning data is used.
The details shown below explain about the "skip function".
[1] Control details
[2] Control precautions
[3] Setting the skip function from the CPU module
[4] Setting the skip function using an external command signal
[1] Control details
The following drawing shows the skip function operation.
BUSYsignal
V
Deceleration by
skip signal
Start of the
next positioning
ON
OFF
OFF
OFF
OFF
ON
ON
ON
Positioning
Positioning start signal
Positioning complete signal
Skip signal
t
[XC, XD, XE, XF]
[Y10, Y11, Y12, Y13]
[X14, X15, X16, X17]
Fig. 12.42 Operation when a skip signal is input during positioning control
[2] Control precautions
(1) If the skip signal is turned ON at the last of an operation, a deceleration stop
will occur and the operation will be terminated.
(2) When a control is skipped (when the skip signal is turned ON during a
control), the positioning complete signals (X14, X15, X16, X17) will not turn
ON.
(3) When the skip signal is turned ON during the dwell time, the remaining dwell
time will be ignored, and the next positioning data will be executed.
(4) When a control is skipped during interpolation control, the reference axis
skip signal is turned ON. When the reference axis skip signal is turned ON,
a deceleration stop will be carried out for every axis, and the next reference
axis positioning data will be executed.
(5) The M code ON signals (X4, X5, X6, X7) will not turn ON when the M code
output is set to the AFTER mode (when "1: AFTER mode" is set in "
Pr.18
M code ON signal output timing").
(In this case, the M code will not be stored in "
Md.25
Valid M code".)
(6) The skip cannot be carried out by the speed control and position-speed
switching control.
(7) If the skip signal is turned ON with the M code signal turned ON, the
transition to the next data is not carried out until the M code signal is turned
OFF.
Summary of Contents for Melsec-Q QD75D1
Page 1: ......
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Page 292: ...MEMO ...
Page 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Page 857: ......
Page 858: ......