13 - 3
MELSEC-Q
13 COMMON FUNCTIONS
13.2 Parameter initialization function
The "parameter initialization function" is used to return the setting data set in the QD75
buffer memory and flash ROM to their factory-set initial values.
The details shown below explain about the "parameter initialization function".
[1] Parameter initialization means
[2] Control details
[3] Control Precautions
[4] Parameter initialization method
[1] Parameter initialization means
• Initialization is executed with a sequence program.
• Initialization is executed by peripheral device.
Refer to GX Configurator-QP Operating Manual for the execution method by
peripheral device.
[2] Control details
The following table shows the setting data initialized by the "parameter
initialization function".
(The data initialized are "buffer memory" and " flash ROM " setting data.)
Setting data
Basic parameters (
Pr.1
to
Pr.10
)
Detailed parameters (
Pr.11
to
Pr.42
,
Pr.150
)
OPR basic parameters (
Pr.43
to
Pr.48
)
OPR detailed parameters (
Pr.49
to
Pr.57
)
Positioning data (No.1 to No.600)
Block start data (No.7000 to No.7004)
[3] Control Precautions
(1) Parameter initialization is only executed when the positioning control is not
carried out (when the PLC READY signal (Y0) is OFF).
The warning "In PLC READY" (warning code: 111) will occur if executed
when the PLC READY [Y0] is ON.
(2) Writing to the flash ROM can be executed up to 100,000 times.
If writing to the flash ROM exceeds 100,000 times, the writing may become
impossible, and the error "Flash ROM write error" (error code: 801) will
occur.
(3) A "CPU module reset" or "CPU module power restart" must be carried out
after the parameters are initialized.
(4) If an error occurs on the parameter set in the QD75 when the PLC READY
signal [Y0] is turned ON, the QD75 READY signal [X0] will not be turned ON
and the control cannot be carried out.
Summary of Contents for Melsec-Q QD75D1
Page 1: ......
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Page 292: ...MEMO ...
Page 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Page 857: ......
Page 858: ......