10 - 15
MELSEC-Q
10 HIGH-LEVEL POSITIONING CONTROL
10.3.7 Repeated start (FOR condition)
In a "repeated start (FOR condition)", the data between the " block start data" in which
"5: FOR condition" is set in "
Da.13
Special start instruction" and the " block start
data" in which "6: NEXT start" is set in "
Da.13
Special start instruction" is repeatedly
executed until the establishment of the conditions set in the "condition data".
Conditional judgment is carried out as soon as switching to the point of "6: NEXT start"
(before positioning of NEXT start point).
(The "condition data" designation is set in "
Da.14
Parameter" of the " block start
data" in which "5: FOR condition" is set in "
Da.13
Special start instruction".)
Section [2] shows a control example where the " block start data" and "positioning
data" are set as shown in section [1].
[1] Setting examples
(1) Block start data setting example
Axis 1 block
start data
Da.11
Shape
Da.12
Start data No.
Da.13
Special start
instruction
Da.14
Parameter
1st point
1: Continue
1
5: FOR condition
5
2nd point
1: Continue
10
0: Block start
–
3rd point
0: End
50
6: NEXT start
–
•
•
The "condition data Nos." have been set in " Da.14 Parameter".
(2) Positioning data setting example
Axis 1 position-
ing data No.
Da.1
Operation pattern
1
01: Continuous positioning control
2
01: Continuous positioning control
3
00: Positioning complete
•
10
11: Continuous path control
11
00: Positioning complete
•
50
01: Continuous positioning control
51
00: Positioning complete
•
[2] Control examples
The following shows the control executed when the " block start data" of the 1st
point of axis 1 is set as shown in section [1] and started.
<1> Execute axis 1 "Positioning data No. 1, 2, 3, 10, 11".
<2> Execute the conditional judgment set in axis 1 "Condition data No.5". 1
Conditions not established Execute "Positioning data No. 50, 51".
Go to <1>
Conditions established Execute "Positioning data No.50, 51" and
complete the positioning.
1: Conditional judgment is carried out as soon as switching to NEXT start point
(before positioning of NEXT start point).
Summary of Contents for Melsec-Q QD75D1
Page 1: ......
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Page 292: ...MEMO ...
Page 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Page 857: ......
Page 858: ......