6 - 41
MELSEC-Q
6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL
[3] Control data requiring setting
Set the following data to execute restart.
Buffer memory address
Setting item
Setting
value
Setting details
Axis 1 Axis 2 Axis 3 Axis 4
Cd.6
Restart command
1
Set "1: Restarts".
1503 1603 1703 1803
Refer to Section 5.7 "List of control data" for details on the setting details.
[4] Starting conditions
The following conditions must be satisfied when restarting. (Assemble the
required conditions into the sequence program as an interlock.)
(1) Operation state
"
Md.26
Axis operation status" is "1: Stopped"
(2) Signal state
Device
Signal name
Signal state
Axis 1 Axis 2 Axis 3 Axis 4
PLC READY signal
ON
CPU module preparation
completed
Y0
QD75 READY signal
ON QD75 preparation completed
X0
Synchronization flag ON
QD75 buffer memory
Accessible
X1
Axis stop signal
OFF Axis stop signal is OFF
Y4
Y5
Y6
Y7
M code ON signal
OFF M code ON signal is OFF
X4
X5
X6
X7
Error detection signal
OFF No error is present
X8
X9
XA
XB
BUSY signal
OFF BUSY signal is OFF
XC
XD
XE
XF
Interface
signal
Start complete signal
OFF Start complete signal is OFF
X10
X11
X12
X13
Drive unit READY signal ON Drive unit preparation completed
–
Stop signal
OFF Stop signal is OFF
–
Upper limit (FLS)
ON Within limit range
–
External
signal
Lower limit (RLS)
ON Within limit range
–
: When the synchronous setting of the CPU module is made in the nonsynchronous mode, this must
be provided as an interlock.
When it is made in the synchronous mode, no interlock must be provided in the program because the
flag is turned ON when calculation is run on the CPU module.
Summary of Contents for Melsec-Q QD75D1
Page 1: ......
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Page 292: ...MEMO ...
Page 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Page 857: ......
Page 858: ......