6 - 36
MELSEC-Q
6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL
[2] Starting by inputting external command signal
When starting positioning control by inputting the external command signal, the
start command can be directly input into the QD75. This allows the variation time
equivalent to one scan time of the CPU module to be eliminated. This is an
effective procedure when operation is to be started as quickly as possible with
the start command or when the starting variation time is to be suppressed. To
start positioning control by inputting the external command signal, set the "data
required to be set" and then turn ON the external command signal.
Restrictions
When starting by inputting the external command signal, the start complete signal
[X10, X11, X12, X13] will not turn ON.
Data required to be set
To execute positioning start with the external command signal, set parameter
(
Pr.42
) beforehand, and validate the "external command signal" with the
"External command function valid setting program (program No. 5)".
Buffer memory address
Setting item
Setting
value
Setting details
Axis 1 Axis 2 Axis 3 Axis 4
Pr.42
External command
function selection
0
Set to "0: External positioning start".
62
212
362
512
Cd.8
External command valid
1
Set to "1: Validate external command".
1505 1605 1705 1805
Refer to CHAPTER 5 "DATA USED FOR POSITIONING CONTROL" for details on the setting details.
Starting time chart
0
V
t
1(00)
External command signal
1
0
1
Cd. 8 External command valid
Dwell time
Operation pattern
Positioning start signal
PLC READY signal
QD75 READY signal
Start complete signal
BUSY signal
Error detection signal
Positioning complete signal
Positioning data No.
Pr. 42 External command function selection
Cd. 3 Positioning start No.
[Y10]
[Y0]
[X0]
[X10]
[XC]
[X14]
[X8]
Fig. 6.11 Time chart for starting with external start signal
Summary of Contents for Melsec-Q QD75D1
Page 1: ......
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Page 292: ...MEMO ...
Page 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Page 857: ......
Page 858: ......