1 - 20
MELSEC-Q
1 PRODUCT OUTLINE
1.2.3 Outline of stopping
Each control is stopped in the following cases.
(1) When each control is completed normally.
(2) When the drive unit READY signal is turned OFF.
(3) When a CPU module error occurs
(4) When the PLC READY signal is turned OFF.
(5) When an error occurs in the QD75.
(6) When control is intentionally stopped (Stop signal from CPU module turned ON,
stop signal from an external device, etc.)
The outline for the stopping process in these cases is shown below. (Excluding (1) for
normal stopping.)
Stop process
OPR control
Manual control
Stop cause
Stop
axis
M code
ON signal
after stop
Axis
operation
status
after
stopping
(
Md.26
)
Machine
OPR
control
Fast
OPR
control
Major
positioning
control
High-level
positioning
control
JOG/
Inching
operation
Manual
pulse
generator
operation
Forced stop
Drive unit
READY
signal OFF
Each
axis
No
change
Error Immediate
stop
Deceleration
stop
Fatal stop
(Stop group 1)
Hardware
stroke limit
upper/lower
limit error
occurrence
Each
axis
No
change
Error
Deceleration stop/sudden stop
(Select with "
Pr.37
Stop group 1 sudden
stop selection")
Deceleration
stop
CPU module
error
occurrence
No
change
PLC READY
signal OFF
Turns
OFF
Emergency
stop
(Stop group 2)
Error in test
mode
All
axes
No
change
Error
Deceleration stop/sudden stop
(Select with "
Pr.38
Stop group 2 sudden
stop selection")
Deceleration
stop
Axis error
detection
(Error other
than stop
group 1 or 2)
1
Relatively safe
stop
(Stop group 3)
"Stop signal"
from
peripheral
device
Each
axis
No
change
Error
"Stop signal"
ON from
external
source
Intentional stop
(Stop group 3) "Axis stop
signal" ON
from CPU
module
Each
axis
No
change
Stopped
(Standby)
Deceleration stop/sudden stop
(Select with "
Pr.39 Stop group 3 sudden
stop selection")
Deceleration
stop
Summary of Contents for Melsec-Q QD75D1
Page 1: ......
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 60: ...2 12 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 137: ...5 33 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 232: ...5 128 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 252: ...6 20 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 253: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 278: ...6 46 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL MEMO ...
Page 292: ...MEMO ...
Page 436: ...9 120 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 464: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 638: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 647: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 686: ...15 48 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 839: ...Appendix 153 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 840: ...Appendix 154 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 841: ...Appendix 155 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 842: ...Appendix 156 MELSEC Q APPENDICES MEMO ...
Page 857: ......