X130
SO1
SO2
16
18
17
SO3
GUID-C5B5FD1C-617B-4F38-A0D4-D98735E69530 V1 EN
Figure 32:
Signal output in BIO0006
3.12
RTD/mA inputs
3.12.1
Functionality
The RTD and mA analog input module is used for monitoring and metering current
(mA), temperature (°C) and resistance (Ω). Each input can be linearly scaled for
various applications, for example, transformer’s tap changer position indication. Each
input has independent limit value supervision and deadband supervision functions,
including warning and alarm signals.
3.12.2
Operation principle
All the inputs of the module are independent RTD and mA channels with individual
protection, reference and optical isolation for each input, making them galvanically
isolated from each other and from the rest of the module. However, the RTD inputs
share a common ground.
3.12.2.1
Selection of input signal type
The function module inputs accept current or resistance type signals. The inputs are
configured for a particular type of input type by the channel-specific
Input mode
setting. The default value for all inputs is “Not in use”, which means that the channel
is not sampled at all, and the output value quality is set accordingly.
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
87
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...