Voltage sensor setting example
The voltage sensor is based on the resistive divider or capacitive divider principle.
Therefore, the voltage is linear throughout the whole measuring range. The output
signal is a voltage, directly proportional to the primary voltage. For the voltage sensor
all parameters are readable directly from its rating plate and conversions are not
needed.
In this example the system phase-to-phase voltage rating is 10 kV. Thus, the
Primary
voltage
parameter is set to 10 kV. For protection relays with sensor measurement
support the
Voltage input type
is always set to “CVD sensor” and it cannot be changed.
The same applies for the
VT connection
parameter which is always set to “WYE” type.
The division ratio for ABB voltage sensors is most often 10000:1. Thus, the
Division
ratio
parameter is usually set to “10000”. The primary voltage is proportionally
divided by this division ratio.
Table 31:
Example setting values for voltage sensor
Setting
Value
Primary voltage
10 kV
VT connection
Wye
Voltage input type
3=CVD sensor
Division ratio
10000
3.10
Binary input
3.10.1
Binary input filter time
The filter time eliminates debounces and short disturbances on a binary input. The
filter time is set for each binary input of the protection relay.
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
79
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...