![ABB RELION Series Technical Manual Download Page 588](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191588.webp)
8.1.11.3
Signals
Table 610:
PEMMXU Input signals
Name
Type
Default
Description
RSTACM
BOOLEAN
0=False
Reset of accumulated energy reading
8.1.11.4
Settings
Table 611:
PEMMXU Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Power unit Mult
3=Kilo
6=Mega
3=Kilo
Unit multiplier for presentation of the
power related values
Energy unit Mult
3=Kilo
6=Mega
3=Kilo
Unit multiplier for presentation of the
energy related values
Active power Dir
1=Forward
2=Reverse
1=Forward
Direction of active power flow: Forward,
Reverse
Reactive power Dir
1=Forward
2=Reverse
1=Forward
Direction of reactive power flow: Forward,
Reverse
Table 612:
PEMMXU Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Forward Wh Initial
0...999999999
1
0
Preset Initial value for forward active
energy
Reverse Wh Initial
0...999999999
1
0
Preset Initial value for reverse active
energy
Forward VArh Initial
0...999999999
1
0
Preset Initial value for forward reactive
energy
Reverse VArh Initial
0...999999999
1
0
Preset Initial value for reverse reactive
energy
Measurement mode
1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
1=PhsA, PhsB,
PhsC
Selected measurement mode for power
calculation
Section 8
1MRS758755 A
Measurement functions
582
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...