Galvanic RJ-45 Ethernet connection
•
Optical LC Ethernet connection
•
ST-type glass fiber serial connection
•
EIA-485 serial connection
•
EIA-232 serial connection
Never touch the end face of an optical fiber connector.
Always install dust caps on unplugged fiber connectors.
If contaminated, clean optical connectors only with fiber-optic
cleaning products.
13.4.1
Ethernet RJ-45 front connection
The protection relay is provided with an RJ-45 connector on the LHMI. The connector
is intended for configuration and setting purposes. The interface on the PC side has to
be configured in a way that it obtains the IP address automatically. There is a DHCP
server inside protection relay for the front interface only.
The events and setting values and all input data such as memorized values and
disturbance records can be read via the front communication port.
Only one of the possible clients can be used for parametrization at a time.
•
PCM600
•
LHMI
•
WHMI
The default IP address of the protection relay through this port is 192.168.0.254.
The front port supports TCP/IP protocol. A standard Ethernet CAT 5 crossover cable
is used with the front port.
The speed of the front connector interface is limited to 10 Mbps.
1MRS758755 A
Section 13
Protection relay's physical connections
REC615 and RER615
767
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...