When the
Operation mode
is set to "Pulsed", the corresponding output can be used to
produce the predefined length of pulses. Once activated, the output remains active for
the duration of the set pulse length. When activated, the additional activation
command does not extend the length of pulse. Thus, the pulse needs to be ended before
the new activation can occur.
The
Description
setting can be used for storing signal names for each output.
Each control point or SPCLGAPC can only be accessed through the LHMI control.
SPCLGAPC follows the local or remote (L/R) state if the
Loc Rem restriction
setting
is "true". If the
Loc Rem restriction
setting is "false", local or remote (L/R) state is
ignored, that is, all controls are allowed regardless of the local or remote state.
The
BLOCK
input can be used for blocking the output functionality. The
BLOCK
input
operation depends on the
Operation mode
setting. If the
Operation mode
setting is set
to "Toggle", the output state cannot be changed when the input
BLOCK
is TRUE. If the
Operation mode
setting is set to "Pulsed", the activation of the
BLOCK
input resets the
output to the FALSE state.
3.16.14.4
Signals
Table 182:
SPCLGAPC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
Table 183:
SPCLGAPC Output signals
Name
Type
Description
O1
BOOLEAN
Output 1 status
O2
BOOLEAN
Output 2 status
O3
BOOLEAN
Output 3 status
O4
BOOLEAN
Output 4 status
O5
BOOLEAN
Output 5 status
O6
BOOLEAN
Output 6 status
O7
BOOLEAN
Output 7 status
O8
BOOLEAN
Output 8 status
O9
BOOLEAN
Output 9 status
O10
BOOLEAN
Output 10 status
O11
BOOLEAN
Output 11 status
O12
BOOLEAN
Output 12 status
O13
BOOLEAN
Output 13 status
O14
BOOLEAN
Output 14 status
O15
BOOLEAN
Output 15 status
O16
BOOLEAN
Output 16 status
Section 3
1MRS758755 A
Basic functions
172
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...