There is also a calculation of the present time to operation with the present current.
This calculation is only performed if the final temperature is calculated to be above the
operation temperature:
t
operate
final
operate
final
n
= − ⋅
−
−
τ
ln
Θ
Θ
Θ
Θ
A070782 V2 EN
(Equation 8)
Caused by the thermal overload protection function, there can be a lockout to
reconnect the tripped circuit after operating. The lockout output
BLK_CLOSE
is
activated at the same time when the
OPERATE
output is activated and is not reset until
the device temperature has cooled down below the set value of the
Reclose
temperature
setting. The
Maximum temperature
value must be set at least two degrees
above the set value of
Reclose temperature
.
The time to lockout release is calculated, that is, the calculation of the cooling time to
a set value. The calculated temperature can be reset to its initial value (the
Initial
temperature
setting) via a control parameter that is located under the clear menu. This
is useful during testing when secondary injected current has given a calculated false
temperature level.
t
lockout
release
final
lockout
release
final
n
_
_
ln
= − ⋅
−
−
τ
Θ
Θ
Θ
Θ
A070783 V3 EN
(Equation 9)
Here the final temperature is equal to the set or measured ambient temperature.
In some applications, the measured current can involve a number of parallel lines. This
is often used for cable lines where one bay connects several parallel cables. By setting
the
Current multiplier
parameter to the number of parallel lines (cables), the actual
current on one line is used in the protection algorithm. To activate this option, the
ENA_MULT
input must be activated.
The ambient temperature can be measured with the RTD measurement. The measured
temperature value is then connected, for example, from the
AI_VAL3
output of the
X130 (RTD) function to the
AMB_TEMP
input of T1PTTR.
The
Env temperature Set
setting is used to define the ambient temperature if the
ambient temperature measurement value is not connected to the
AMB_TEMP
input.
The
Env temperature Set
setting is also used when the ambient temperature
measurement connected to T1PTTR is set to “Not in use” in the X130 (RTD) function.
The temperature calculation is initiated from the value defined with the
Initial
temperature
setting parameter. This is done in case the protection relay is powered up,
the function is turned "Off" and back "On" or reset through the Clear menu. The
temperature is also stored in the nonvolatile memory and restored in case the
protection relay is restarted.
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
255
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...