exceeds the limit value set with the
LO Acc currents Pwr
threshold setting, the
IPOW_LO
output is activated.
The
IPOW_ALM
and
IPOW_LO
outputs can be blocked by activating the binary input
BLOCK
.
7.1.4.6
Remaining life of circuit breaker
Every time the breaker operates, the life of the circuit breaker reduces due to wearing.
The wearing in the breaker depends on the tripping current, and the remaining life of
the breaker is estimated from the circuit breaker trip curve provided by the
manufacturer. The remaining life is decremented at least with one when the circuit
breaker is opened.
The operation of the remaining life of the circuit breaker subfunction can be described
with a module diagram. All the modules in the diagram are explained in the next
sections.
A071111 V2 EN
Figure 288:
Functional module diagram for estimating the life of the circuit
breaker
Circuit breaker life estimator
The circuit breaker life estimator module calculates the remaining life of the circuit
breaker. If the tripping current is less than the rated operating current set with the
Rated Op current
setting, the remaining operation of the breaker reduces by one
operation. If the tripping current is more than the rated fault current set with the
Rated
fault current
setting, the possible operations are zero. The remaining life of the
tripping current in between these two values is calculated based on the trip curve given
by the manufacturer. The
Op number rated
and
Op number fault
parameters set the
number of operations the breaker can perform at the rated current and at the rated fault
current, respectively.
The remaining life is calculated separately for all three phases and it is available as a
monitored data value
CB_LIFE_A (_B,_C)
. The values can be cleared by setting
the parameter
CB wear values
in the clear menu from WHMI or LHMI.
Clearing
CB wear values
also resets the operation counter.
1MRS758755 A
Section 7
Condition monitoring functions
REC615 and RER615
543
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...