4.4.4.9
Technical data
Table 446:
NSPTOV Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the voltage
measured: f
n
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 1.1 × set
Start
value
U
Fault
= 2.0 × set
Start
value
33 ms
24 ms
35 ms
26 ms
37 ms
28 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) Negative-sequence voltage before fault = 0.0 × U
n
, f
n
= 50 Hz, negative-sequence overvoltage with
nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
4.4.4.10
Technical revision history
Table 447:
NSPTOV Technical revision history
Technical revision
Change
B
Internal change
C
Internal improvement.
D
Internal improvement.
4.4.5
Positive-sequence undervoltage protection PSPTUV
4.4.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Positive-sequence undervoltage
protection
PSPTUV
U1<
47U+
Section 4
1MRS758755 A
Protection functions
430
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...