4.2.7.6
Signals
Table 385:
MFADPSDE Input signals
Name
Type
Default
Description
Io
SIGNAL
0
Residual current
Uo
SIGNAL
0
Residual voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
RELEASE
BOOLEAN
0=False
External trigger to release neutral admittance
protection
RESET
BOOLEAN
0=False
External trigger to reset direction calculatio
Table 386:
MFADPSDE Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
BLK_EF
BOOLEAN
Block signal for EF to indicate opposite direction
peaks
INTR_EF
BOOLEAN
Intermittent earth-fault indication
PEAK_IND
BOOLEAN
Current transient detection indication
4.2.7.7
Settings
Table 387:
MFADPSDE Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Directional mode
2=Forward
3=Reverse
2=Forward
Directional mode
Voltage start value
0.01...1.00
xUn
0.01
0.10
Voltage start value
Operate delay time
60...1200000
ms
10
500
Operate delay time
Table 388:
MFADPSDE Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Operating quantity
1=Adaptive
2=Amplitude
3=Resistive
1=Adaptive
Operating quantity selection
Min operate current
0.005...5.000
xIn
0.001
0.010
Minimum operate current
Tilt angle
2.0...20.0
deg
0.1
5.0
Characteristic tilt angle
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
393
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...