![ABB RELION Series Technical Manual Download Page 713](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191713.webp)
Name
Type
Values (Range)
Unit
Description
Max unbalance Volt
FLOAT32
0.00...150.00
%
Maximum 3 seconds
unbalance voltage
Time Max Unb Volt
Timestamp
Time stamp of maximum
voltage unbalance
Alarm high mean Dur FLOAT32
0.000...3600.000
s
Time duration for alarm
high mean unbalance
Max unbalance Volt
FLOAT32
0.00...150.00
%
Maximum 3 seconds
unbalance voltage
Time Max Unb Volt
Timestamp
Time stamp of maximum
voltage unbalance
VSQVUB
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
10.4.9
Technical data
Table 706:
VSQVUB Technical data
Characteristic
Value
Operation accuracy
±1.5% of the set value or ±0.002 × U
n
Reset ratio
Typically 0.96
1MRS758755 A
Section 10
Power quality measurement functions
REC615 and RER615
707