Figure 251:
Description of the equivalent load distance
The exact value for
Equivalent load Dis
can be calculated based on the load flow and
voltage drop calculations using data from DMS-system and the following equation.
Equivalent load Dis
U
U
d real
d tap d
=
=
(
)
(
,
)
1
GUID-E447E8AC-65F7-4586-B853-C297347303FF V2 EN
(Equation 50)
U
d(real)
The actual maximum voltage drop of the feeder
U
d(tap,d=1)
The fictional voltage drop, if the entire load would be tapped at the end (d=1) of the
feeder (not drawn in
). The calculation of this value requires data from
the DMS system.
Alternatively, the setting
Equivalent load Dis
can be determined by conducting a
single-phase earth-fault test (R
fault
= 0 Ω) at that point of the feeder where the
maximum actual voltage drop takes place. This point is typically located at the end of
the main line. As a result, the calculated value is stored in the recorded data Equivalent
load Dis.
In addition, when the setting
EF algorithm Sel
is equal to “Load modelling”, the
EF
algorithm Cur Sel
setting determines whether zero-sequence “Io based” or negative-
sequence “I2 based” current based algorithm is used. The difference between “Io
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
487
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...