Parameter
Values (Range)
Unit
Step
Default
Description
Num of phases
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=1 out of 3
Number of phases required for voltage
supervision
V live value
0.2...1.0
xUn
0.1
0.5
Limit value for high voltage
V live time
40...10000
ms
1
100
Duration time for high voltage
V dead value
0.1...0.8
xUn
0.1
0.2
Limit value for low voltage
V dead time
40...10000
ms
1
100
Duration time for low voltage
Table 553:
PHSVPR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Relative hysteresis
1.0...5.0
%
0.1
4.0
Relative hysteresis for voltage
supervision
6.4.8
Monitored data
Table 554:
PHSVPR Monitored data
Name
Type
Values (Range)
Unit
Description
PHSVPR
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
6.4.9
Technical data
Table 555:
PHSVPR Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Operation time accuracy
±1.0% of the set value or ±20 ms
Section 6
1MRS758755 A
Supervision functions
534
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...