Table 329:
DEFHPDEF Input signals
Name
Type
Default
Description
Io
SIGNAL
0
Residual current
Uo
SIGNAL
0
Residual voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
ENA_MULT
BOOLEAN
0=False
Enable signal for current multiplier
RCA_CTL
BOOLEAN
0=False
Relay characteristic angle control
Table 330:
DEFLPDEF Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
Table 331:
FDEFLPDEF Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
Table 332:
DEFHPDEF Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.2.2.11
Settings
Table 333:
DEFLPDEF Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.010...5.000
xIn
0.005
0.010
Start value
Start value Mult
0.8...10.0
0.1
1.0
Multiplier for scaling the start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward
Directional mode
Time multiplier
0.05...15.00
0.01
1.00
Time multiplier in IEC/ANSI IDMT curves
Table continues on next page
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
305
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...