networks where the neutral point is earthed through a low resistance, the characteristic
angle is always 0º.
As the amplitude of the residual current is independent of the fault location, the
selectivity of the earth-fault protection is achieved with time coordination.
The use of wattmetric protection gives a possibility to use the dedicated inverse
definite minimum time characteristics. This is applicable in large high-impedance
earthed networks with a large capacitive earth-fault current.
In a network employing a low-impedance earthed system, a medium-size neutral point
resistor is used. Such a resistor gives a resistive earth-fault current component of about
200...400 A for an excessive earth fault. In such a system, the directional residual
power protection gives better possibilities for selectivity enabled by the inverse time
power characteristics.
4.2.6.8
Signals
Table 378:
WPWDE Input signals
Name
Type
Default
Description
Io
SIGNAL
0
Residual current
Uo
SIGNAL
0
Residual voltage
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
RCA_CTL
BOOLEAN
0=False
Relay characteristic angle control
Table 379:
WPWDE Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
4.2.6.9
Settings
Table 380:
WPWDE Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Directional mode
2=Forward
3=Reverse
2=Forward
Directional mode
Current start value
0.010...5.000
xIn
0.001
0.010
Minimum operate residual current for
deciding fault direction
Voltage start value
0.010...1.000
xUn
0.001
0.010
Start value for residual voltage
Power start value
0.003...1.000
xPn
0.001
0.003
Start value for residual active power
Reference power
0.050...1.000
xPn
0.001
0.150
Reference value of residual power for
Wattmetric IDMT curves
Characteristic angle
-179...180
deg
1
-90
Characteristic angle
Table continues on next page
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
371
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...