functions are designed according to the IEC 61850-7-4 standard with logical nodes
CILO, CSWI and XSWI/XCBR.
The circuit breaker and disconnector control functions have an operation counter for
closing and opening cycles. The counter value can be read and written remotely from
the place of operation or via the LHMI.
9.1.4
Operation principle
Status indication and validity check
The object state is defined by two digital inputs,
POSOPEN
and
POSCLOSE
, which
are also available as outputs
OPENPOS
and
CLOSEPOS
together with the
OKPOS
. The debouncing and short disturbances in an input are
eliminated by filtering. The binary input filtering time can be adjusted separately for
each digital input used by the function block. The validity of the digital inputs that
indicate the object state is used as additional information in indications and event
logging. The reporting of faulty or intermediate position of the apparatus occurs after
the
Event delay
setting, assuming that the circuit breaker is still in a corresponding
state.
Table 628:
Status indication
Input
Status
Output
POSOPEN
POSCLOSE
POSITION
(Monitored
data)
OKPOS
OPENPOS
CLOSEPOS
1=True
0=False
1=Open
1=True
1=True
0=False
0=False
1=True
2=Closed
1=True
0=False
1=True
1=True
1=True
3=Faulty/Bad
(11)
0=False
0=False
0=False
0=False
0=False
0=Intermediat
e (00)
0=False
0=False
0=False
Enabling and blocking
CBXCBR and DCXSWI have an enabling and blocking functionality for interlocking
and synchrocheck purposes.
Circuit breaker control CBXCBR
Normally, the CB closing is enabled (that is,
CLOSE_ENAD
signal is TRUE) by
activating both
ENA_CLOSE
and
SYNC_OK
inputs. Typically, the
ENA_CLOSE
comes from the interlocking, and
SYNC_OK
comes from the synchronism and
energizing check. The input
SYNC_ITL_BYP
can be used for bypassing this control.
The
SYNC_ITL_BYP
input can be used to activate
CLOSE_ENAD
discarding the
ENA_CLOSE
and
SYNC_OK
input states. However, the
BLK_CLOSE
input always
blocks the
CLOSE_ENAD
output.
Section 9
1MRS758755 A
Control functions
604
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...