![ABB RELION Series Technical Manual Download Page 645](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191645.webp)
•
First reclose time
= 1.0s
•
Init signals CBB1
= 7 (three lowest bits: 111000 = 7)
•
Blk signals CBB1
= 16 (the fifth bit: 000010 = 16)
•
Shot number CBB1
= 1
CBB2 settings are:
•
Second reclose time
= 10s
•
Init signals CBB2
= 6 (the second and third bits: 011000 = 6)
•
Blk signals CBB2
= 16 (the fifth bit: 000010 = 16)
•
Shot number CBB2
= 2
CBB3 settings are:
•
Third reclose time
= 30s
•
Init signals CBB3
= 4 (the third bit: 001000 = 4)
•
Blk signals CBB3
= 16 (the fifth bit: 000010 = 16)
•
Shot number CBB3
= 3
CBB4 settings are:
•
Fourth reclose time
= 0.5s
•
Init signals CBB4
= 8 (the fourth bit: 000100 = 8)
•
Blk signals CBB4
= 0 (no blocking signals related to this CBB)
•
Shot number CBB4
= 1
If a shot is initiated from the
INIT_1
line, only one shot is allowed before lockout.
If a shot is initiated from the
INIT_3
line, three shots are allowed before lockout.
A sequence initiation from the
INIT_4
line leads to a lockout after two shots. In a
situation where the initiation is made from both the
INIT_3
and
INIT_4
lines, a
third shot is allowed, that is, CBB3 is allowed to start. This is called conditional
lockout. If the initiation is made from the
INIT_2
and
INIT_3
lines, an immediate
lockout occurs.
The
INIT_5
line is used for blocking purposes. If the
INIT_5
line is active during
a sequence start, the reclose attempt is blocked and the AR function goes to lockout.
If more than one CBBs are started with the shot pointer, the CBB with
the smallest individual number is always selected. For example, if the
INIT_2
and
INIT_4
lines are active for the second shot, that is, the
shot pointer is 2, CBB2 is started instead of CBB5.
Even if the initiation signals are not received from the protection functions, the AR
function can be set to continue from the second to the fifth reclose shot. The AR
function can, for example, be requested to automatically continue with the sequence
when the circuit breaker fails to close when requested. In such a case, the AR function
1MRS758755 A
Section 9
Control functions
REC615 and RER615
639
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...