Audit trail is a chronological record of system activities that allows the reconstruction
and examination of the sequence of system and security-related events and changes in
the protection relay. Both audit trail events and process related events can be
examined and analyzed in a consistent method with the help of Event List in LHMI
and WHMI and Event Viewer in PCM600.
The protection relay stores 2048 audit trail events to the nonvolatile audit trail.
Additionally, 1024 process events are stored in a nonvolatile event list. Both the audit
trail and event list work according to the FIFO principle. Nonvolatile memory is based
on a memory type which does not need battery backup nor regular component change
to maintain the memory storage.
Audit trail events related to user authorization (login, logout, violation remote and
violation local) are defined according to the selected set of requirements from IEEE
1686. The logging is based on predefined user names or user categories. The user audit
trail events are accessible with IEC 61850-8-1, PCM600, LHMI and WHMI.
Table 4:
Audit trail events
Audit trail event
Description
Configuration change
Configuration files changed
Firmware change
Firmware changed
Firmware change fail
Firmware change failed
Attached to retrofit test case
Unit has been attached to retrofit case
Removed from retrofit test case
Removed from retrofit test case
Setting group remote
User changed setting group remotely
Setting group local
User changed setting group locally
Control remote
DPC object control remote
Control local
DPC object control local
Test on
Test mode on
Test off
Test mode off
Reset trips
Reset latched trips (TRPPTRC*)
Setting commit
Settings have been changed
Time change
Time changed directly by the user. Note that this is not used
when the protection relay is synchronised properly by the
appropriate protocol (SNTP, IRIG-B, IEEE 1588 v2).
View audit log
Administrator accessed audit trail
Login
Successful login from IEC 61850-8-1 (MMS), WHMI, FTP or
LHMI.
Logout
Successful logout from IEC 61850-8-1 (MMS), WHMI, FTP or
LHMI.
Password change
Password changed
Firmware reset
Reset issued by user or tool
Audit overflow
Too many audit events in the time period
Violation remote
Unsuccessful login attempt from IEC 61850-8-1 (MMS),
WHMI, FTP or LHMI.
Violation local
Unsuccessful login attempt from IEC 61850-8-1 (MMS),
WHMI, FTP or LHMI.
Section 2
1MRS758755 A
REC615 and RER615 overview
36
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...