parameter to "1" and connecting the protection start information to the corresponding
DEL_INIT_
input.
When the function detects a closing of the circuit breaker, that is, any other closing
except the reclosing done by the function itself, it always prohibits shot initiation for
the time set with the
Reclaim time
parameter. Furthermore, if the
Fourth delay in
SOTF
parameter is "1", the
Str _ delay shot 4
parameter delays are also activated.
Example 1
The protection operation time is 0.5 seconds, the
Fourth delay in SOTF
parameter is
set to "1" and the
Str 2 delay shot 4
parameter is 0.05 seconds. The protection start
signal is connected to the
DEL_INIT_2
input.
If the protection starts after the circuit breaker closes, the fast trip follows after the set
0.05 seconds. The total trip time is the protection start delay + 0.05 s the time
it takes to open the circuit breaker.
9.4.7
Signals
Table 667:
DARREC Input signals
Name
Type
Default
Description
INIT_1
BOOLEAN
0=False
AR initialization / blocking signal 1
INIT_2
BOOLEAN
0=False
AR initialization / blocking signal 2
INIT_3
BOOLEAN
0=False
AR initialization / blocking signal 3
INIT_4
BOOLEAN
0=False
AR initialization / blocking signal 4
INIT_5
BOOLEAN
0=False
AR initialization / blocking signal 5
INIT_6
BOOLEAN
0=False
AR initialization / blocking signal 6
DEL_INIT_2
BOOLEAN
0=False
Delayed AR initialization / blocking signal 2
DEL_INIT_3
BOOLEAN
0=False
Delayed AR initialization / blocking signal 3
DEL_INIT_4
BOOLEAN
0=False
Delayed AR initialization / blocking signal 4
BLK_RECL_T
BOOLEAN
0=False
Blocks and resets reclose time
BLK_RCLM_T
BOOLEAN
0=False
Blocks and resets reclaim time
BLK_THERM
BOOLEAN
0=False
Blocks and holds the reclose shot from the thermal
overload
CB_POS
BOOLEAN
0=False
Circuit breaker position input
CB_READY
BOOLEAN
1=True
Circuit breaker status signal
INC_SHOTP
BOOLEAN
0=False
A zone sequence coordination signal
INHIBIT_RECL
BOOLEAN
0=False
Interrupts and inhibits reclosing sequence
RECL_ON
BOOLEAN
0=False
Level sensitive signal for allowing (high) / not
allowing (low) reclosing
SYNC
BOOLEAN
0=False
Synchronizing check fulfilled
Section 9
1MRS758755 A
Control functions
660
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...