![ABB RELION Series Technical Manual Download Page 550](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191550.webp)
Alarm limit check
When the remaining life of any phase drops below the
Life alarm level
threshold
setting, the corresponding circuit breaker life alarm
CB_LIFE_ALM
is activated.
It is possible to deactivate the
CB_LIFE_ALM
alarm signal by activating the binary
input
BLOCK
. The old circuit breaker operation counter value can be taken into use by
writing the value to the
Initial CB Rmn life
parameter and resetting the value via the
clear menu from WHMI or LHMI.
7.1.4.7
Circuit breaker spring-charged indication
The circuit breaker spring-charged indication subfunction calculates the spring
charging time.
The operation of the subfunction can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
A071112 V3 EN
Figure 289:
Functional module diagram for circuit breaker spring-charged
indication and alarm
Spring charge time measurement
Two binary inputs,
SPR_CHR_ST
and
SPR_CHR
, indicate spring charging started
and spring charged, respectively. The spring-charging time is calculated from the
difference of these two signal timings.
The spring charging time
T_SPR_CHR
is available in the monitored data view on the
LHMI or through tools via communications.
Alarm limit check
If the time taken by the spring to charge is more than the value set with the
Spring
charge time
setting, the subfunction generates the
SPR_CHR_ALM
alarm.
It is possible to block the
SPR_CHR_ALM
alarm signal by activating the
BLOCK
binary input.
7.1.4.8
Gas pressure supervision
The gas pressure supervision subfunction monitors the gas pressure inside the arc
chamber.
Section 7
1MRS758755 A
Condition monitoring functions
544
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...