Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the
BLOCK
input and the global setting in
Configuration/System/
Blocking mode
which selects the blocking mode. The
BLOCK
input can be controlled
by a binary input, a horizontal communication input or an internal signal of the
protection relay's program. The influence of the
BLOCK
signal activation is
preselected with the global setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode,
the operation timer is frozen to the prevailing value, but the
OPERATE
output is not
deactivated when blocking is activated. In the "Block all" mode, the whole function is
blocked and the timers are reset. In the "Block OPERATE output" mode, the function
operates normally but the
OPERATE
output is not activated.
4.7.5
Application
The function block can be used for any general analog signal protection, either
underprotection or overprotection. The setting range is wide, allowing various
protection schemes for the function. Thus, the absolute hysteresis can be set to a value
that suits the application.
The temperature protection using the RTD sensors can be done using the function
block. The measured temperature can be fed from the RTD sensor to the function input
that detects too high temperatures in the motor bearings or windings, for example.
When the
ENA_ADD
input is enabled, the threshold value of the internal comparator
is the sum of the
Start value Add
and
Start value
settings. This allows a temporal
increase or decrease of the level detector depending on the sign and value of the
Start
value Add
setting, for example, when the emergency start is activated. If, for example,
Start value
is 100,
Start value Add
is 20 and the
ENA_ADD
input is active, the input
signal needs to rise above 120 before MAPGAPC operates.
4.7.6
Signals
Table 484:
MAPGAPC Input signals
Name
Type
Default
Description
AI_VALUE
FLOAT32
0.0
Analogue input value
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
ENA_ADD
BOOLEAN
0=False
Enable start added
Table 485:
MAPGAPC Output signals
Name
Type
Description
OPERATE
BOOLEAN
Operate
START
BOOLEAN
Start
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
459
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...