Figure 261:
An example of the ALARM output use
5.4.4.5
Recorded data
All the information required for a later fault analysis is recorded to SCEFRFLO
recorded data. In the protection relay, recorded data is found in
Monitoring/
Recorded data/Other protection/SCEFRFLO
.
The function has also monitored data values which are used for the read-out of
continuous calculation values. The cross reference table shows which of the recorded
data values are available as continuous monitoring values during a fault.
Table 519:
Cross reference table for recorded and monitored data values
Recorded data
Monitored data
Flt loop
FAULT_LOOP
Flt distance
FLT_DISTANCE
Flt Dist quality
FLT_DIST_Q
Flt loop resistance
RFLOOP
Flt loop reactance
XFLOOP
Flt phase reactance
XFPHASE
Flt point resistance
RF
Flt to Lod Cur ratio
IFLT_PER_ILD
Equivalent load Dis
S_CALC
XC0F Calc
XC0F_CALC
5.4.4.6
Measurement modes
The full operation of SCEFRFLO requires that all three phase-to-earth voltages are
measured. The voltages can be measured with conventional voltage transformers or
voltage dividers connected between the phase and earth (
VT connection
is set to
“Wye”). Another alternative is to measure phase-to-phase voltages (
VT connection
is
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
501
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...