3.19.1.4
Settings
Table 198:
Redundancy settings
Parameter
Values (Range) Unit
Step
Default Description
Redundant
mode
None
PRP
HSR
None
Mode selection for Ethernet switch on
redundant communication modules.
The "None" mode is used with normal
and Self-healing Ethernet topologies.
3.19.1.5
Monitored data
Monitored data is available in four locations.
•
Monitoring/Communication/Ethernet/Activity/CHLIV_A
•
Monitoring/Communication/Ethernet/Activity/REDCHLIV_B
•
Monitoring/Communication/Ethernet/Link statuses/LNKLIV_A
•
Monitoring/Communication/Ethernet/Link statuses/REDLNKLIV_B
3.19.2
Ethernet channel supervision SCHLCCH
3.19.2.1
Function block
GUID-DBA25BB9-6BF5-4C45-A39F-1920113A22F2 V1 EN
Figure 112:
Function block
3.19.2.2
Functionality
Ethernet channel supervision SCHLCCH represents X1/LAN, X2/LAN and X3/LAN
Ethernet channels.
An unused Ethernet port can be set "Off" with the setting
Configuration/
Communication/Ethernet/Rear port(s)/Port x Mode
. This setting closes the port
from software, disabling the Ethernet communication in that port. Closing an unused
Ethernet port enhances the cyber security of the relay.
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
197
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...