A070441 V1 EN
Figure 146:
Earth-fault situation in an isolated network
Directional earth-fault protection in a compensated network
In compensated networks, the capacitive fault current and the inductive resonance coil
current compensate each other. The protection cannot be based on the reactive current
measurement, since the current of the compensation coil would disturb the operation
of the protection relays. In this case, the selectivity is based on the measurement of the
active current component. The magnitude of this component is often small and must
be increased by means of a parallel resistor in the compensation equipment. When
measuring the resistive part of the residual current, the relay characteristic angle
(RCA) should be set to 0 degrees and the operation criteria to "IoCos" or "Phase
angle".
illustrates a simplified equivalent circuit for a compensated
network with an earth fault in phase C.
A070444 V2 EN
Figure 147:
Earth-fault situation in a compensated network
The Petersen coil or the earthing resistor may be temporarily out of operation. To keep
the protection scheme selective, it is necessary to update the
Characteristic angle
setting accordingly. This can be done with an auxiliary input in the protection relay
which receives a signal from an auxiliary switch of the disconnector of the Petersen
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
289
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...