![ABB RELION Series Technical Manual Download Page 590](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191590.webp)
Name
Type
Values (Range)
Unit
Description
Max demand S
FLOAT32
-999999.9...9999
99.9
kVA
Maximum demand value
of apparent power
Min demand S
FLOAT32
-999999.9...9999
99.9
kVA
Minimum demand value
of apparent power
Max demand P
FLOAT32
-999999.9...9999
99.9
kW
Maximum demand value
of active power
Min demand P
FLOAT32
-999999.9...9999
99.9
kW
Minimum demand value
of active power
Max demand Q
FLOAT32
-999999.9...9999
99.9
kVAr
Maximum demand value
of reactive power
Min demand Q
FLOAT32
-999999.9...9999
99.9
kVAr
Minimum demand value
of reactive power
Time max dmd S
Timestamp
Time of maximum
demand
Time min dmd S
Timestamp
Time of minimum
demand
Time max dmd P
Timestamp
Time of maximum
demand
Time min dmd P
Timestamp
Time of minimum
demand
Time max dmd Q
Timestamp
Time of maximum
demand
Time min dmd Q
Timestamp
Time of minimum
demand
8.1.11.6
Technical data
Table 614:
PEMMXU Technical data
Characteristic
Value
Operation accuracy
At all three currents in range 0.10…1.20 × I
n
At all three voltages in range 0.50…1.15 × U
n
At the frequency f
n
±1 Hz
±1.5% for apparent power S
±1.5% for active power P and active energy
1)
±1.5% for reactive power Q and reactive energy
2)
±0.015 for power factor
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1) |PF| >0.5 which equals |cosφ| >0.5
2) |PF| <0.86 which equals |sinφ| >0.5
Section 8
1MRS758755 A
Measurement functions
584
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...