The load profile record consists of two COMTRADE file types: the configuration file
(.CFG) and the data file (.DAT). The file name is same for both file types.
To ensure that both the uploaded file types are generated from the same data content,
the files need to be uploaded successively. Once either of the files is uploaded, the
recording buffer is halted to give time to upload the other file.
Data content of the load profile record is sequentially updated.
Therefore, the size attribute for both COMTRADE files is "0".
192 . 168 .
10
.
187
L D P 1
0 A
B B
L D P 1 . C F G
0 A
B B
L D P 1 . D A T
GUID-43078009-323D-409C-B84A-5EB914CDEE53 V1 EN
Figure 110:
Load profile record file naming
3.18.2.4
Clearing of record
The load profile record can be cleared with
Reset load profile rec
via HMI,
communication or the ACT input in PCM600. Clearing of the record is allowed only
on the engineer and administrator authorization levels.
The load profile record is automatically cleared if the quantity selection parameters
are changed or any other parameter which affects the content of the COMTRADE
configuration file is changed. Also, if data source for selected quantity is removed, for
example, with ACT, the load profile recorder stops recording and previously collected
data are cleared.
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
181
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...